Preventive maintenance
Scheduled inspections, cleaning, torque and thermal checks, filter and fan service, and firmware updates, to the manufacturer’s maintenance schedule.
Commissioning, maintenance, repair and testing on utility-scale solar and storage plants, closed out with a signed test report.
From first checks through utility backfeed, performance testing and utility witness testing, we follow the manufacturer’s procedure and document every result, so the plant goes into service with a complete commissioning report.
Insulation resistance, wire tightness and torque checks on busbar and cable terminations, equipment and arc-flash label verification, fuse size verification and enclosure inspection.
DC polarity checks, auxiliary power-up, firmware and parameter setup, Modbus register mapping, utility backfeed, grid synchronization, reactive-power settings, plant performance testing and utility witness tests.
Commissioning, maintenance and repair experience on equipment from these manufacturers. Ask about other platforms; we’ll tell you plainly whether we’ve worked on them.


Scheduled inspections, cleaning, torque and thermal checks, filter and fan service, and firmware updates, to the manufacturer’s maintenance schedule.
Fault-finding and component replacement on inverters and PCS: power modules, contactors, fuses, fans, control boards and cooling parts.
Warranty diagnostics, part replacements and retrofits performed for equipment manufacturers, with the documentation they require.
Baseline tests at commissioning and condition checks during operation, so problems show up before a failure takes a block offline.
Radiometric surveys of switchgear, combiners, inverters and terminations to find hot spots before they fail.
Class A logging of harmonics, sags, swells and unbalance, checked against IEEE 519 and the interconnection requirements.
VLF withstand and tan delta testing on medium-voltage cable, and fault location on DC and medium-voltage runs.
Field failures go through an 8D investigation. You get a written report with the evidence, not just a replaced part.
Contain the problem.
Collect the data.
Find the root cause.
Verify the root cause.
Correct it and confirm the fix.
| Test | Typical equipment | Reference | You receive |
|---|---|---|---|
| Inverter cold and hot commissioning | 1500 V-rated meter, insulation tester, Modbus laptop | Manufacturer procedure; IEEE 1547 commissioning requirements | Commissioning report with string voltage and polarity log and as-left settings |
| Insulation, turns ratio and winding resistance | Insulation tester, TTR test set, micro-ohmmeter | IEEE C57.12.90; ANSI/NETA ATS | IR, PI and DAR values; ratio error; winding resistance by tap |
| Sweep frequency response (SFRA) | SFRA analyzer | IEEE C57.149; IEC 60076-18 | Frequency response traces and comparison to baseline |
| Transformer oil (DGA) | Sampling kit; accredited third-party lab | ASTM D923; ASTM D3612; IEEE C57.104 | Lab report: dissolved gases, moisture and oil quality |
| Infrared thermography | Radiometric infrared camera | ANSI/NETA MTS | Thermal images with temperature-rise ratings |
| Medium-voltage cable testing | VLF test set | IEEE 400.2 | Withstand and tan delta results |
We check that construction matches the drawings, the manufacturer’s instructions and the NEC.